One Shot Universal Liquitreat
Part No. RXSOL-50-5001-020
Scale and Corrosion control by one shot operation
It is a well - balanced blend for boiler water treatment products, resulting in a scale and corrosion control by one shot operation. A powdered one-step treatment to control the formation of rust and scale in low pressure and auxillary boilers with w
Key Technical Details
| Part number | RXSOL-50-5001-020 |
|---|---|
| Generic name | Scale and Corrosion control by one shot operation |
| IMPA code | 551091 |
| Standard packing | 20.00 |
| Available pack sizes | 18 / 25 / 35 / 210 Ltr. |
| Supply locations | One Shot Universal Liquitreat manufacturer supplier distributor in Mumbai, Kandla, Kolkata, Vizag, Chennai, India, Fujairah, Dubai UAE, Muscat Oman, Kenya Africa. Get the best quality of One Shot Universal Liquitreat at a competitive price from us. We have ready stock of One Shot Universal Liquitreat in India, UAE Gulf, Oman, Kenya Africa. Contact us for bulk as well as small orders. |
The dosage rate is dependent on bioler operating condition, feed 2-3 ltrs of RXSOL-50-5001-020 solution for per thousand ltr of bioler water then control the system by periodic Alkalinity test procedure. If p-Alkalinity is below 200 ppm increase the ratio of rxsol BWT 5001 solution. If p-Alkalinity is above 400 ppm reduce the concentration of RXSOL-50-5001-020 solution by dilution with water. RXSOL-50-5001-020 is strongly alkaline.RXSOL-50-5001-020 is best applied heat or diluted with any convenient strength on a continuous basis using a suitable chemicals pump. The product should be applied to the boiler feed tank or feed line to ensure adequate mixing.
CHARACTERISTIC :
- Convenient liquid treatment, which provides the basic alkalinity on which successful water treatment depends.
- Provides optimum conditions for hardness control to function.
- Neutralizes acid conditions.
- Will assist in keeping silica in suspension.
- Simple test to determine level of treatment.
- Can be used in boilers of all pressures.
- Can be used as a neutralizer after acid cleaning operations
- Suitable for use with all auxiliary boilers; waste heat units; economizers, package boilers, smoke and water tube boilers.
- Dispersant action suspends sludge and sediment particles for efficient blow down.
- Oxygen scavenging for optimum protection.
- Protects boiler, steam lines, condensate lines and feed water lines from corrosion.
- Fast action due to catalyst.
- Simple test to determine level of treatment.
Basic Boiler System Schematic
Below is a summary of problems associated with the common impurities in water and solutions to each problem.
List Of Problems Caused By Impurities In Water
|
Impurity (Chemical Formula) |
Problems |
Common Chemical Treatment Methods |
|
Alkalinity (HCO3-, CO32- and CaCO3) |
Carryover of feedwater into steam, produce CO2 in steam leading to formation of carbonic acid (acid attack) |
Neutralizing amines, filming amines, combination of both, and lime-soda. |
|
Hardness (calcium and magnesium salts, CaCO3) |
Primary source of scale in heat exchange equipment |
Lime softening, phosphate, chelates and polymers |
|
Iron (Fe3+ and Fe2+) |
Causes boiler and water line deposits |
Phosphate, chelates and polymers |
|
Oxygen (O2) |
Corrosion of water lines, boiler, return lines, heat exchanger equipments, etc. (oxygen attack) |
Oxygen scavengers, filming amines and deaeration |
|
pH |
Corrosion occurs when pH drops below 8.5 |
pH can be lowered by addition of acids and increased by addition of alkalies |
|
Hydrogen Sulfide (H2S) |
Corrosion |
Chlorination |
|
Silica (SiO2) |
Scale in boilers and cooling water systems |
Lime softening |