Hardness Control Liquid

Deck cabin galley Maintenance-25

Hardness Control Liquid

Phosphate bsed Corrosion inhibitor and hardness conditioner

Liquid product used for the reduction of hardness in boilers. Hardness Control is highly soluble in water and It will precipitate calcium hardness as a non-adherent sludge.

Key details

Generic name Phosphate bsed Corrosion inhibitor and hardness conditioner
IMPA code 551441
Active matter (%) 72-81
Standard packing 25.00 Ltr.
Available pack sizes Boiler water hardness resulting tuff scale in side the system tubes, which becomes very tuff to remove. So its prior treatment with HARDNESS control is wise decision. We are keeping ready stock of material in 25, 50 Ltr packing.
Supply locations Hardness Control Liquid is one of classified Boiler water treatment liquid useful to avoid scale formation in Boiler. We are popular Hardness Control Liquid manufacturer and supplier in Mumbai, Kandla - Gandhidham, Chennai - Ennore, Kolkata - Haldia, Visakhapatnam, Fujairah - Dubai - Abudhabi, Sharjah.

Need this product at your port or plant?

Enquire Now
Application

Hardness Control is formulated to form a precipitate with calcium ions which will not adhere to metal surfaces but are in a form suitable for blowdown.

 

Using Procedure

For optimum results dose Hardness Control direct to the boiler via the bypass pot-feeder. The dry powder should be dissolved in hot water (50°C) at a ratio of 1 part powder to twenty parts condensate (e.g. 500 grams/10 litres). Ensure that treatment is fully dissolved before dosing.

Dosage and control

 

 

Phophate test result in pPM PO4

 

 Pressure

 0 - 10

10 - 20

20 - 30

30 - 40

40 - 50

> 50

 Control range

 0-40 Bar
0-588 PSI

 23

11.5 

Satisfactory

Satisfactory

Blow Down

 20-50

41-60 Bar
589-880 PSI 

 17

 5.5

Satisfactory

Blow Down

Blow Down

  15-30

 > 60 Bar
> 880 PSI

 5.5

 Satisfactory

Satisfactory

Blow Down

Blow Down

 10-25

Select row on righthand side for applicable pressure range. Compare test result with comment in table and dose stated amount of product per ton boiler water volume.

These are recommended values based on experience and are in no way intended to replace the boiler manufacturer's specifications or company regulations.

 

Technical Specifications

Sampling And Testing

A sample of boiler water should be drawn for analysis daily. The sample should always be taken from the same point after blow down, cooled and tested immediately. Follow the Rxsol Hardness Test Kit instructions and fill the Boiler Water Log Form according to result results. It is important that regular testing is carried out to ensure levels of treatment are correct.

Physical Properties :

Appearance        :MILKY LIQ
Corrosive action  : non
pH 1% solution   : 8,8
Flash point         : none

Note

Benefit and Features

  • Highly active phosphate based compound, economical in use.
  • Easily dissolved in water for dosing.
  • Scale problems due to calcium are eliminated.
  • Maintains sludge in a non-adherent state for ease of blow down.
  • Simple test to determine level of treatment.
  • Can be used for boilers of all pressures.
    Rxsol Hardness Control does not influence the alkalinity in the system